병원 건물에 설치된 냉각탑 병용 지열 히트펌프 시스템의 냉방 성능
기관명 | NDSL |
---|---|
저널명 | 한국지열에너지학회논문집 = Transactions of the Korea society of geothermal energy engineers |
ISSN | 1738-6985, |
ISBN |
저자(한글) | 손병후,이두영,민경천 |
---|---|
저자(영문) | |
소속기관 | |
소속기관(영문) | |
출판인 | |
간행물 번호 | |
발행연도 | 2016-01-01 |
초록 | This paper presents the measurement and analysis results for the cooling performance of ground-coupled heat pump (GCHP) system using a cooling tower as a supplemental heat rejector. In order to demonstrate the performance of the hybrid approach, we installed the monitoring equipments including sensors for measuring temperature and power consumption, and measured operation parameters from May 1 to October 30, 2014. The results showed that the entering source temperature of brine returning from the ground heat exchanger was in a range of design target temperature. Leaving load temperatures to building showed an average value of $11.4^{ circ}C$ for cooling season. From the analysis, the daily performance factor (PF) of geothermal heat pumps ranged from 4.4 to 5.2, while the daily PF of hybrid GCHP system varied from 3.0 to 4.0 over the entire cooling season. |
원문URL | http://click.ndsl.kr/servlet/OpenAPIDetailView?keyValue=03553784&target=NART&cn=JAKO201613752757775 |
첨부파일 |
과학기술표준분류 | |
---|---|
ICT 기술분류 | |
DDC 분류 | |
주제어 (키워드) | 하이브리드 지열 히트펌프 시스템,냉방 성능,냉각탑,측정,Hybrid ground-coupled heat pump system,Cooling performance,Cooling tower,Measurement |